国家电网公司物资采购标准 (交流变压器卷 10kV变压器册)

10kV三相干式变压器

专用技术规范

(编号:1001002-0010-02)

目 次

1 标准技术参数表 ·········································································································· 27 2 项目需求部分 ············································································································· 29 2.1 货物需求及供货范围 ··································································································· 29 2.2 必备的备品备件、专用工具和仪器仪表··············································································· 29 2.3 图纸资料提交单位 ······································································································ 29 2.4 工程概况 ················································································································ 30 2.5 使用条件 ················································································································ 30 2.6 可选技术参数表 ········································································································ 30 2.7 项目单位技术差异表 ··································································································· 31 3 投标人响应部分 ·········································································································· 31 3.1 投标人应提供的信息 ··································································································· 31 3.2 投标人技术偏差表 ······································································································ 32 3.3 投标人应提供的其他资料 ······························································································ 32

1 标准技术参数表

投标人应认真逐项填写技术参数和性能要求响应表中投标人保证值,不能空格,也不能以“响应”两字代替,不允许改动招标人要求值。如有偏差,应填写技术偏差表。“投标人保证值”应与型式试验报告相符。

表1 技术参数和性能要求响应表

序号 一 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 二 1 2 3 4 三 1 2 四 1 五 1 100%额定电压时 额定频率额定电压时空载损耗 额定电流下的绕组平均温升(F) 额定电流下的绕组平均温升(H) 高压绕组雷电全波冲击电压(峰值) 高压绕组雷电截波冲击电压(峰值) 高压绕组额定短时工频耐受电压(有效值) 低压绕组额定短时工频耐受电压(有效值) 变压器型号 铁心材质 线圈结构 高压绕组 低压绕组 联结组 额定频率 额定容量 相数 调压方式 调压位置 调压范围 中性点接地方式 冷却方式 磁通密度 绝缘耐热等级 局部放电水平 名 称 单位 额定值 kV kV Hz kVA T pC 绝缘水平 kV kV kV 温升限值 K 空载损耗 kW 空载电流 % 见附表1 (投标人填写) 见附表1 (投标人填写) 100 125 (投标人填写) 75 85 35 5 (投标人填写) (投标人填写) (投标人填写) (投标人填写) 见表6 冷轧取向硅钢片 见表6 见附表1 0.4 见附表1 50 见附表1 3 见附表1 高压侧 见附表1 不接地 见表6 (投标人提供) F级及以上 ≤10 (投标人填写) (投标人填写) (投标人填写) (投标人填写) (投标人填写) (投标人填写) (投标人填写) (投标人填写) (投标人填写) (投标人填写) (投标人填写) (投标人填写) (投标人填写) (投标人填写) (投标人填写) (投标人填写) (投标人填写) 标准参数值 投标人保证值 表1(续)

序号 六 1 七 八 1 总质量 主分接(75℃) 噪声水平 名 称 单位 负载损耗 kW dB 质量和尺寸 t (投标人提供) (投标人填写) 见附表1 见附表2 (投标人填写) (投标人填写) 标准参数值 投标人保证值 注 附表1和附表2是本表的补充部分。

附表1 标准参数表

A组 变压器 容量 (kVA) 50 100 160 200 315 500 630 630 800 1000 1250 2000 2500 变压器 容量 (kVA) 315 500 630 630 800 1000 1250 2000 2500 有载 10 10.5 ±4×2.5 0.4 Dyn11 Yyn0 调压 方式 高压 (kV) 高压分接 范围 (%) 低压 电压 (kV) 联结组 标号 无励磁 10 10.5 ±5 ±2×2.5 调压 方式 高压 (kV) 高压分接范围 (%) 低压 电压 (kV) 联结组 标号 空载损耗 (kW) 0.27 0.4 0. 0.62 0.88 1..16 0.4 Dyn11 Yyn0 1.340 1.300 1..52 1.77 2.09 3.05 3.60 负载损耗F(120℃)(kW) 1.0 1.57 2.13 2.53 3.47 4.88 5.88 5.960 6.96 8.13 9.69 15.96 18. B组 空载损耗 (kW) 0.34 0.36 0.49 0.58 0.78 1.040 1.200 1.160 1.37 1.56 1.81 2.70 3.15 负载损耗F(120℃)(kW) 1.07 1.69 2.32 2.69 3.69 5.16 6.140 6.330 7.38 8.73 10.39 16.72 19.84 空载电流 (%) 短路 阻抗 (%) 空载电流 (%) 6.0 4.0 短路 阻抗 (%) 6 4 空载损耗(kW) 负载损耗F(120℃) (kW) 3.61 5.23 6.18 6.37 7.98 8.79 10.45 14.34 18.15 0.99 1.30 1.494 1.44 1.71 1.98 2.34 3.42 3.96 附表2 噪 声 水 平

变压器容量(kVA) 轨距A×B(mm×mm) 噪声水平(dB) 50 100 160 550×550 550×550 550×550 65 66 附表2(续)

变压器容量(kVA) 200 315 500 630 800 1000 1250 2000 2500 轨距A×B(mm×mm) 660×550 660×660 660×660 820×820 820×820 820×820 1070×820 — — 噪声水平(dB) 67 69 70 71 72 72 74 77 78 2 项目需求部分

2.1 货物需求及供货范围

货物需求及供货范围一览表见表2。

表2 货物需求及供货范围一览表

序号 1 2 3 4 项目单位要求 变压器型号 主要参数 单位 数量 变压器型号 投标人响应 主要参数 单位 数量 2.2 必备的备品备件、专用工具和仪器仪表

必备的备品备件、专用工具和仪器仪表供货表见表3。

表3 必备的备品备件、专用工具和仪器仪表供货表

序号 1 2 3 4 5 名 称 单 位 项目单位要求 型号和规格 数量 投标人响应 型号和规格 数量 2.3 图纸资料提交单位

需确认的图纸资料应由卖方提交到表4所列的单位。

表4 卖方提交的需经确认的图纸资料及其接收单位

提交图纸、资料名称 认可图、最终图 接收图纸单位名称、地址、邮编、电话 (设计单位) 提交份数 (附电子文档) 认可图、最终图 说明书 试验报告 (附电子文档) (项目单位) 2.4 工程概况

2.4.1 项目名称: 2.4.2 项目单位: 2.4.3 交通、运输: 2.5 使用条件

使用条件参数表见表5。

表5 使用条件参数表

序号 1 2 3 4 5 6 名 称 额定电压 最高运行电压 系统中性点接地方式 额定频率 污秽等级 系统短路电流水平(高压侧) 最高日温度 最低日温度 7 环境温度 最大日温差 最热月平均温度 最高年平均温度 8 9 10 11 12 13 14 湿度 海拔 太阳辐射强度 最大覆冰厚度 离地面高10m处,维持10min的平均最大风速 耐受地震能力 地面水平加速度 正弦共振三个周期安全系数 安装场所(户内) 日相对湿度平均值 月相对湿度平均值 单位 kV kV Hz kA ℃ K ℃ 招标人要求值 10 12 不接地 50 Ⅲ 20 40 25 25 +30 +20 ≤95 ≤90 ≤1000 0.1 20 35 2 ≥1.67 (项目单位提供) % m W∕cm2 mm m/s m/s2 注 1. 环境最低气温超过25℃的需要进行温度修正。

2. 污秽等级为Ⅳ级的需提供该地区的污秽等级图。 3. 有关海拔、污秽、温度的修正情况见表7。

2.6 可选技术参数表

可选技术参数表见表6。

表6 可选技术参数表

序号及 名称 1 2 项 目 变压器型号 线圈结构 标准参数值 环氧浇注式、包封式、敞开式 招标人要求值 (项目单位提供) (项目单位提供) 投标人保证值 (投标人填写) (投标人填写) 表6(续)

序号及 名称 3 4 5 6 项 目 冷却方式 联结组 调压方式 高压分接范围 …… 标准参数值 AN或AN/AF Dyn11或Yyn0 无励磁、有载 ±5%或 ±2×2.5% 招标人要求值 (项目单位提供) (项目单位提供) (项目单位提供) (项目单位提供) 投标人保证值 (投标人填写) (投标人填写) (投标人填写) (投标人填写) 2.7 项目单位技术差异表

项目单位原则上不能改动通用部分条款及专用部分固化的参数,根据工程实际情况,使用条件及相关技术参数如有差异,应逐项在项目单位技术差异表中列出。

表7 项目单位技术差异表(项目单位填写)

(本表是对技术规范的补充和修改,如有冲突,应以本表为准)

序号 1 2 序号 1 2 项 目 …… 项 目 …… 标准参数值 变更条款页码、款号 项目单位要求值 原表述 投标人保证值 变更后表述 3 投标人响应部分

3.1 投标人应提供的信息

投标人应提供的信息见表8~表10。

表8 销售运行业绩表

序号 1 2 型号规格 数量 用户单位 用户联系人 用户联系人电话 投运时间 备注 3 4 5 6 7 表9 推荐的备品备件、专用工具和仪器仪表供货表(投标人填写)

序号 1 2 3 4 5 6 名 称 型号和规格 单位 数量 表10 主要部件材料表

序号 1 2 3 4 5 6 7 名 称 冷轧取向硅钢片 高压线圈导线 低压线圈导线 分接开关 温控器 其他需要说明的材料及附件 绝缘材料 …… 型号、规格、厂家、原产地 招标人要求 投标人响应 备 注 3.2 投标人技术偏差表

投标人提供的产品技术规范应完全满足本招标文件中的规定。若有偏差,投标人应如实、认真地在技术偏差表(见表11)中填写偏差值,否则视为与本招标文件中规定的要求一致。若无技术偏差,则应在技术偏差表中填写“无偏差”。

表11 投标人技术偏差表

序号 1 2 3 项 目 对应条款编号 技术招标文件要求 偏 差 备 注 3.3 投标人应提供的其他资料 3.3.1 用户运行证明。

3.3.2 同类产品鉴定证书及鉴定产品的型式试验报告(见表12和表13)。

表12 投标人提供的鉴定证书表

序号 鉴定产品型号名称 …… 组织鉴定单位 依据标准 鉴定时间 表13 投标人提供的试验检测报告表

序号 产品型号名称 …… 试验报告类别和 内容 依据标准 试验时间 试验单位 3.3.3 投标人需提供的设备图纸及资料

投标文件中投标人应提供以下图纸及资料: 1) 说明书。 2) 试验报告。